DETAILED PARAMETER DESCRIPTION<br />
Possible Values<br />
Factory<br />
Standard<br />
P22 - Rated current of the Soft-Starter<br />
120, 170, 205, 255, 290, 340, 410, 475,<br />
580, 670, 800, 950, 1100, 1400A<br />
According<br />
to the<br />
type<br />
NOTE!<br />
1) When a Soft-Starter is connected within the motor delta<br />
connection (P28=ON), the rated current of the Soft-<br />
Starter is set automatically to 1.73 x IN, of the Soft-Starter.<br />
2) Do not change this value, since the content of this<br />
parameter is specific for each software.<br />
6.3.12 - P23 - Rated<br />
voltage of the<br />
Soft-Starter (V)<br />
<br />
The function is to calculate the power supplied to the<br />
load.<br />
Possible Values<br />
Factory<br />
Standard<br />
P23 - Rated voltage of the Soft-Starter<br />
220, 230, 240, 380, 400, 415,<br />
440, 460, 480, 525, 575V<br />
380<br />
6.3.13 - P31 - Phase<br />
rotation<br />
(ON = RST;<br />
OFF = any<br />
sequence)<br />
This function can be enabled or disabled, but when<br />
enabled its function is to protect the loads that can<br />
not be driven in both directions of rotation.<br />
NOTE!<br />
The phase sequence is only detected at the first time when<br />
the power part is activated after the electronic part has<br />
been energized. Thus a new phase sequence can only be<br />
detected when the electronic part is switched OFF or reset.<br />
Possible Values<br />
Factory<br />
Standard<br />
P31 - Phase rotation<br />
OFF, ON<br />
OFF<br />