04.04.2019 Views

ssw03_plus_series

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

6<br />

DETAILED PARAMETER DESCRIPTION<br />

Possible Values<br />

Factory<br />

Standard<br />

P22 - Rated current of the Soft-Starter<br />

120, 170, 205, 255, 290, 340, 410, 475,<br />

580, 670, 800, 950, 1100, 1400A<br />

According<br />

to the<br />

type<br />

NOTE!<br />

1) When a Soft-Starter is connected within the motor delta<br />

connection (P28=ON), the rated current of the Soft-<br />

Starter is set automatically to 1.73 x IN, of the Soft-Starter.<br />

2) Do not change this value, since the content of this<br />

parameter is specific for each software.<br />

6.3.12 - P23 - Rated<br />

voltage of the<br />

Soft-Starter (V)<br />

<br />

The function is to calculate the power supplied to the<br />

load.<br />

Possible Values<br />

Factory<br />

Standard<br />

P23 - Rated voltage of the Soft-Starter<br />

220, 230, 240, 380, 400, 415,<br />

440, 460, 480, 525, 575V<br />

380<br />

6.3.13 - P31 - Phase<br />

rotation<br />

(ON = RST;<br />

OFF = any<br />

sequence)<br />

This function can be enabled or disabled, but when<br />

enabled its function is to protect the loads that can<br />

not be driven in both directions of rotation.<br />

NOTE!<br />

The phase sequence is only detected at the first time when<br />

the power part is activated after the electronic part has<br />

been energized. Thus a new phase sequence can only be<br />

detected when the electronic part is switched OFF or reset.<br />

Possible Values<br />

Factory<br />

Standard<br />

P31 - Phase rotation<br />

OFF, ON<br />

OFF<br />

65<br />

Downloaded from www.Manualslib.com manuals search engine

Hooray! Your file is uploaded and ready to be published.

Saved successfully!