DETAILED PARAMETER DESCRIPTION<br />
6.4.5 -P50 - Function<br />
of the Relay RL3<br />
<br />
It enables the Relay RL3 to operate according to the<br />
parameters set below:<br />
1- The N.O. contact from RL3 is closed when the<br />
SSW-03 Plus does not have a fault condition.<br />
2- The N.O. contact from RL3 is closed when the<br />
SSW-03 Plus have a fault condition.<br />
P50 - Programming of the Relay RL3<br />
Possible Values<br />
1, 2<br />
Factory<br />
Standard<br />
1<br />
6.4.6 - P51 - Function<br />
of the relay RL1<br />
<br />
It enables the Relay RL1 to operate according to the<br />
parameters set below:<br />
1 - Function “Operation”, the relay is switched ON<br />
instantaneously with the order Switch ON of the Soft-<br />
Starter, switching Off only when the Soft-Starter<br />
receives an order of general switching Off, or by<br />
ramp when the voltage reaches 30% of the rated voltage<br />
(30% UN), as shown in Figure 6.7.<br />
2 - Full voltage Function, the relay is only switched On<br />
after Soft-Starter has reached 100% of UN, and<br />
switched Off when the Soft-Starter receives a<br />
command for general switching Off, or by ramp, as<br />
shown in Figure 6.7.<br />
NOTE!<br />
The function of full voltage is used to activate the by-pass<br />
contactor, the parameter P43 must be set at "On".<br />
UN<br />
100%<br />
Relay On<br />
Operation<br />
function<br />
Full Voltage<br />
function<br />
Figure 6.7 - Functioning of the relays RL1 and RL2<br />
t<br />
t<br />
t<br />