DETAILED PARAMETER DESCRIPTION<br />

6.4.5 -P50 - Function<br />

of the Relay RL3<br />

<br />

It enables the Relay RL3 to operate according to the<br />

parameters set below:<br />

1- The N.O. contact from RL3 is closed when the<br />

SSW-03 Plus does not have a fault condition.<br />

2- The N.O. contact from RL3 is closed when the<br />

SSW-03 Plus have a fault condition.<br />

P50 - Programming of the Relay RL3<br />

Possible Values<br />

1, 2<br />

Factory<br />

Standard<br />

1<br />

6.4.6 - P51 - Function<br />

of the relay RL1<br />

<br />

It enables the Relay RL1 to operate according to the<br />

parameters set below:<br />

1 - Function “Operation”, the relay is switched ON<br />

instantaneously with the order Switch ON of the Soft-<br />

Starter, switching Off only when the Soft-Starter<br />

receives an order of general switching Off, or by<br />

ramp when the voltage reaches 30% of the rated voltage<br />

(30% UN), as shown in Figure 6.7.<br />

2 - Full voltage Function, the relay is only switched On<br />

after Soft-Starter has reached 100% of UN, and<br />

switched Off when the Soft-Starter receives a<br />

command for general switching Off, or by ramp, as<br />

shown in Figure 6.7.<br />

NOTE!<br />

The function of full voltage is used to activate the by-pass<br />

contactor, the parameter P43 must be set at "On".<br />

UN<br />

100%<br />

Relay On<br />

Operation<br />

function<br />

Full Voltage<br />

function<br />

Figure 6.7 - Functioning of the relays RL1 and RL2<br />

t<br />

t<br />

t<br />

76<br />