DETAILED PARAMETER DESCRIPTION<br />
P55 - Programming of the Digital Input<br />
4 (DI4)<br />
Possible Values<br />
OFF, 1, 2, 3, 4<br />
Factory<br />
Standard<br />
OFF<br />
6.4.11 - P56 - Programming<br />
of the analog<br />
output<br />
This parameter enables the analog 8 bits output (X2:8<br />
and X2:9) (Voltage 0...10Vdc - gain adjustable at P57)<br />
and indicates the following magnitudes:<br />
OFF = Without Programming<br />
1 - "Current": proportional to the current that flows through the<br />
switch.<br />
2 - "Voltage" proportional to the SSW-03 Plus output voltage.<br />
3 - "Power Factor": porportional to the power factor of the load<br />
without considering the harmonic currents.<br />
4 - "Thermal motor protection": proportional to the thermal state<br />
of the motor.<br />
P56 - Programming of the Analog<br />
output (8 bits)<br />
Possible Values<br />
OFF, 1, 2, 3, 4<br />
Factory<br />
Standard<br />
OFF<br />
6.4.12 - P57 - Scaling<br />
of the Analog<br />
Output<br />
This parameter sets the scaling of the analog output<br />
(X2:8 and X2:9) that is defined by the parameter P56.<br />
NOTE!<br />
With gain 1.00 we will have the following conditions:<br />
P56 = 1<br />
P56 = 2<br />
P56 = 3<br />
P56 = 4<br />
Output: 10 Vdc, when 500% of the IN of the Soft-Starter.<br />
Output: 10 Vdc when 100% of the UN of the Soft-Starter<br />
output.<br />
Output: 10 Vdc when the load power factor is equal to<br />
1.00.<br />
Output: 10 Vdc when the state of the thermal protection<br />
of the motor (P82) is equal to 250%.<br />