<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

5.9.4 Technology Modules<br />

Table 45:<br />

XN-1CNT-24VDC<br />

XN-1CNT-24VDC<br />

Diagnosis<br />

byte<br />

n<br />

When bit 7 = 0<br />

(counter<br />

mode)<br />

n<br />

When bit 7 = 1<br />

(Measurement<br />

mode)<br />

Bit Diagnosis<br />

0 Short-circuit / open circuit → ERR_DO<br />

1 Short-circuit in sensor power supply→ ERR-<br />

24VDC<br />

2 End of counter range wrong<br />

3 Start of counter range wrong<br />

4 Invert-DI+latch-retr. not perm.<br />

It is not permitted to invert the level of the<br />

digital input when using the latch-retriggerfunction<br />

5 Main count direction wrong<br />

6 Operating mode wrong<br />

7 Measurement mode<br />

Bit = 0 Conter mode active<br />

0 Short-circuit / open circuit → ERR_DO<br />

1 Short-circuit in sensor power supply →<br />

ERR-24VDC<br />

2 Sensor pulse wrong<br />

3 Integration time wrong<br />

4 Upper limit wrong<br />

5 Lower limit wrong<br />

6 Operating mode wrong<br />

7 Messbetriebsart<br />

Bit = 1 measurement operation is active<br />

108 M001973-01, 07/2007