<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

5.8 Parameters of the Modules<br />

5.8.1 Analog input modules<br />

Table 14:<br />

Module<br />

parameters<br />

A Defaultsettings<br />

Table 15:<br />

Module<br />

parameters<br />

A Defaultsettings<br />

XN-1AI-I(0/4...20MA)<br />

Byte Bit Parameter<br />

name<br />

Value<br />

– Meaning<br />

0 0 current mode 0 = 0...20 mA A<br />

1 value<br />

representation<br />

1 = 4...20 mA<br />

0 = Integer (15 bit + sign) A<br />

1 = 12 bit (left justified)<br />

2 diagnosis 0 = activate A<br />

1 = deactivate<br />

XN-2AI-I(0/4...20MA) (1 byte parameter per channel)<br />

Byte Bit Parameter<br />

name<br />

Value<br />

– Meaning<br />

0/1 0 current mode 0 = 0...20 mA A<br />

1 value<br />

representation<br />

1 = 4...20 mA<br />

0 = Integer (15 bit + sign) A<br />

1 = 12 bit (left justified)<br />

2 diagnosis 0 = activate A<br />

1 = deactivate<br />

3 channel 0 = activate A<br />

1 = deactivate<br />