<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

A Defaultsettings<br />

Byte Bit Parameter<br />

name<br />

Value<br />

– Meaning<br />

0 7 diagnosis 0 = release A<br />

1 = block<br />

1 0 stop bits 0 = 1 bit A<br />

1 = 2 bit<br />

2,1 parity 00 = none<br />

01 = odd A<br />

– The number of the bits set (data<br />

bits and parity bit) is odd.<br />

10 = even<br />

– The number of the bits set (data<br />

bits and parity bit) is even.<br />

3 data bits 0 = 7 A<br />

– The number of data bits is 7.<br />

1 = 8<br />

– The number of data bits is 8.<br />

2 X<strong>ON</strong>-character 0 – 255 (17 A)<br />

– Only in RS422-mode:<br />

This character is used to start<br />

the data transfer of the data<br />

terminal device (DTE) when the<br />

software-handshake is activated<br />

3 XOFF-character 0 – 255 (19 A)<br />

– Only in RS422-mode:<br />

This character is used to stop<br />

the data transfer of the data<br />

terminal device (DTE) when the<br />

software-handshake is activated<br />