<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 6 Application example: Modbus TCP<br />

6.3.4 Reading-out the process image length (inputs)<br />

Intelligent modules<br />

The process image length of the intelligent input modules is read via<br />

function code 04 from register 1011:<br />

Figure 53:<br />

Process image<br />

length (intelligent<br />

input modules)<br />

Table 52:<br />

Process input<br />

data of intelligent<br />

modules<br />

The process image length of the intelligent input modules is:<br />

0×90 bits = 18 bytes = 9 registers<br />

Module Process input<br />

0 XN-2AI-I(0/4...20MA) 2<br />

3 XN-2AI-THERMO-PI 2<br />

6 XN-1AI-U(-10/0...+10VDC) 1<br />

9 XN-1SSI 4<br />

Total 9<br />

Words/ registers<br />

128 M001973-01, 07/2007