<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

5.8.3 Technology modules<br />

Table 24:<br />

Module<br />

parameters<br />

A Default<br />

settings<br />

XN-1CNT-24VDC, Counter mode<br />

Byte Bit Parameter<br />

name<br />

0 0 to<br />

5<br />

Value<br />

– Meaning<br />

Counter mode 100000 = continous countA<br />

100001 = single-action count<br />

100010 = periodical count<br />

1 0 gate function 0 = abort count procedure A<br />

1 = interrupt count procedure<br />

1 digital input DI 0 = normal A<br />

1 = inverted<br />

2/3 Function DI 00 = input A<br />

01 = HW-gate<br />

10 = Latch-retrigger when edge<br />

positive<br />

11 = Synchronization when edge<br />

positive<br />

4 Synchronization 0 = single-actionA<br />

1 = periodical<br />

5/6 Main count<br />

dirextion<br />

2 to 5 Lower count<br />

limit<br />

Lower count<br />

limit (HWORD)<br />

Lower count<br />

limit (LWORD)<br />

00 = none A<br />

01 = up<br />

10 = down<br />

-2 147 483 648 (-2 31 ) to 0<br />

-32768 A to 0 (Signed16)<br />

-32 768 to 32 767<br />

(Signed16); 0 A<br />

M001973-01, 07/2007 89