<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 4 Technical Features<br />

4.5.6 Address setting via PGM-mode<br />

Figure 27:<br />

PGM-mode<br />

The PGM-mode enables the access of I/O-ASSISTANTs to the<br />

module’s network settings.<br />

In order to activate the PGM-mode, the rotary coding-switches have<br />

to be set to "500".<br />

9<br />

8<br />

0<br />

7<br />

6<br />

5<br />

1<br />

2<br />

3<br />

4<br />

Adr. × 10<br />

Adr. × 100<br />

9<br />

8<br />

0<br />

7<br />

6<br />

9 1<br />

8 2<br />

7 3<br />

6<br />

5<br />

4<br />

0<br />

Adr. × 1<br />

Note<br />

In the PGM-mode, all network settings (IP address, subnet mask,<br />

etc.) are read from the module’s internal EEPROM.<br />

The settings carried out in the rotary-mode are stored in the<br />

module’s non-volatile EEPROM.<br />

4.5.7 Addressing via PGM-DHCP<br />

5<br />

The addressing of the <strong>XI</strong>/<strong>ON</strong> Modbus TCP gateway via PGM-DHCP<br />

is at the moment comparable to the addressing via DHCP (see<br />

Chapter 4.5.5 „Address setting via DHCP-mode”, Page 41).<br />

M001973-01, 07/2007 43<br />

1<br />

2<br />

3<br />

4<br />

Set<br />

000 : 192.168.1.254<br />

1-254 : Static rotary<br />

300 : BootP<br />

400 : DHCP<br />

500 : PGM<br />

600 : PGM-DHCP