06.03.2013 Views

Product Description XI/ON - Eaton Automation

Product Description XI/ON - Eaton Automation

Product Description XI/ON - Eaton Automation

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

5.3 Modbus Registers<br />

Table 7:<br />

Modbus registers<br />

of the gateway<br />

A ro = read only<br />

rw = read/write<br />

Note<br />

Table 8: „Mapping of XN-GW-EN Modbus registers (holding registers)”,<br />

Page 63 shows the register mapping for the different Modbus<br />

addressing methods.<br />

Address<br />

(hex.)<br />

0×0000 to<br />

0×01FF<br />

0×0800 to<br />

0×09FF<br />

0×1000 to<br />

0×1006<br />

Access<br />

A<br />

<strong>Description</strong><br />

ro packed process data of inputs<br />

(process data length of modules, see<br />

Table 9: „Data width of the I/O-modules”,<br />

Page 70)<br />

rw packed process data of outputs<br />

(process data length of modules, see<br />

Table 9: „Data width of the I/O-modules”,<br />

Page 70)<br />

ro gateway identifier<br />

0×100C ro gateway status (see Table 10: „Register<br />

100Ch: gateway-status”, Page 72)<br />

0×1010 ro process image length in bit for the intelligent<br />

output modules<br />

0×1011 ro process image length in bit for the intelligent<br />

input modules<br />

0×1012 ro process image length in bit for the digital<br />

output modules<br />

0×1013 ro process image length in bit for the digital<br />

input modules<br />

0×1017 ro register-mapping revision (always 1, if<br />

not, mapping is incompatible with this<br />

description)<br />

60 M001973-01, 07/2007