<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 7 Guidelines for Station Planning<br />

7.2 Power Supply<br />

7.2.1 Module Bus Refreshing<br />

The number of <strong>XI</strong>/<strong>ON</strong> modules that can be supplied by the gateway<br />

or a separate Bus Refreshing module via the internal module bus<br />

depends on the respective nominal current consumption of the individual<br />

modules on the module bus.<br />

Attention<br />

The sum total of the nominal current consumption of the connected<br />

<strong>XI</strong>/<strong>ON</strong> modules must not exceed 1.5 A.<br />

The following examples show the calculation for the required<br />

number of Bus Refreshing modules:<br />

Example 1:<br />

The <strong>XI</strong>/<strong>ON</strong> station consists of 20 XN-1AI-I(0/4...20MA) modules. The<br />

number of additional Bus Refreshing modules required is calculated<br />

as follows:<br />

Gateway 430 mA<br />

20 XN-1AI-I(0/4...20MA) 20 x 41 mA 820 mA<br />

Total: 1250 mA<br />

Maximum permissible current via module bus: 1 500 mA<br />

The calculation shows that no further Bus Refreshing module is<br />

required.<br />

152 M001973-01, 07/2007