<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 6 Application example: Modbus TCP<br />

6.5.2 Module diagnosis (0×A000 to 0×A400)<br />

For each module, 64 Bytes = 32 registes are reserved for diagnostic<br />

messages.<br />

Module 3: XN-2AI-THERMO-PI<br />

The module has 2 bytes of diagnosis data, these are shown in<br />

register 0×A060<br />

→ register 0×A060 = 0×0200<br />

→ "open circuit" at channel 1.<br />

Figure 64:<br />

module diagnosis,<br />

module 3<br />

A diagnosis byte<br />

channel 0<br />

B diagnosis byte<br />

channel 1<br />

Table 60:<br />

XN-2AI-<br />

THERMO-PI<br />

Diagnosis<br />

byte<br />

Bit Diagnosis<br />

A threshold:<br />

1% of the positive<br />

n 0 measurement value range error A<br />

measurement range<br />

1 open circuit B<br />

end value<br />

B Threshold: 5 W<br />

(only in temperature measurement ranges)<br />

(loop resistance)<br />

2 to 7 reserved<br />

M001973-01, 07/2007 147<br />