<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

Table 13:<br />

results of the<br />

service request<br />

A service request may have the following results:<br />

Service code Meaning<br />

0×0000 error free execution of service<br />

0×FFFE service parameters<br />

incorrect/ inconsistent<br />

0×FFFF service code unknown<br />

Note<br />

The services "indirect reading of registers" and "indirect writing of<br />

registers" offer an additional possibility to access any Modbus<br />

register.<br />

Current Modbus-masters support only a limited number of registerareas<br />

that can be read or written during the communication with a<br />

Modbus-server. These areas can not be changed during operation.<br />

In this case, the services mentioned above enables non-cyclic access<br />

to registers.<br />

5.6.1 Indirect reading of registers<br />

1 to 122 (Count) Modbus-registers are read, starting with address<br />

x (Addr).<br />

service-request<br />

2000h 2001h 2002h 2003h 2004h 2005h 207Fh<br />

service<br />

no.<br />

service-response<br />

0×0000 0×0003 Addr Count reserved<br />

2080h 2081h 2082h 2083h 2084h 2085h 20FFh<br />

service<br />

no.<br />

result 0×0003 Addr Count register contents<br />