<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 9 Appendix<br />

Table 69:<br />

Meaning of the<br />

data bits<br />

(process output)<br />

Designation Value Meaning<br />

RXBUF FLUSH 0 - 1 This bit is used to flush the receivebuffer.<br />

If STATRES = 1:<br />

The command RXBUF FLUSH = 1 is<br />

ignored.<br />

If STATRES = 0:<br />

RXBUF FLUSH = 1 causes the flushing<br />

of the receive-buffer.<br />

TXBUF FLUSH 0-1 This bit is used to flush the transmitbuffer.<br />

If STATRES = 1:<br />

The command TXBUF FLUSH = 1 is<br />

ignored.<br />

If STATRES = 0:<br />

TXBUF FLUSH = 1 causes the flushing<br />

of the tranceive-buffer.<br />

STATRES 0-1 This bit is set to reset the STAT bit in the<br />

process input data.<br />

With the change from 1 to 0 the STAT bit<br />

is reset (from 0 to 1).<br />

If this bit is 0, all changes in<br />

TX_BYTE_CNT, TX_CNT and<br />

RX_CNT_ACK are ignored.<br />

Flushing the transmit-/ receive-buffer<br />

with RXBUF FLUSH/ TXBUF FLUSH is<br />

possible.<br />

If this bit is 1 or with the change from 0<br />

to 1, the flushing of the transmit-/<br />

receive-buffer with RXBUF FLUSH/<br />

TXBUF FLUSH is not possible.<br />

M001973-01, 07/2007 197