<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 4 Technical Features<br />

4.5.2 Default setting of the gateway<br />

Figure 23:<br />

Decimal rotary<br />

coding-switches<br />

for the address<br />

setting<br />

The gateway’s default-settings are the following:<br />

IP address 192.168.1.254<br />

subnet mask 255.255.255.000<br />

default gateway 192.168.1.001<br />

Note<br />

The gateway can be reset to these default settings by the user at any<br />

time.<br />

To reset the gateway, please set the three coding-switches at the<br />

gateway to "000" followed by a power-on reset.<br />

Adr. × 100<br />

9<br />

8<br />

0<br />

7<br />

6<br />

9 1<br />

8 2<br />

7<br />

6<br />

5<br />

3<br />

4<br />

0<br />

9 1<br />

8 2<br />

7<br />

6<br />

5<br />

3<br />

4<br />

0<br />

Adr. × 10 Adr. × 1<br />

5<br />

Attention<br />

After every change of the address-mode, a voltage reset must be<br />

carried out.<br />

38 M001973-01, 07/2007<br />

1<br />

2<br />

3<br />

4<br />

Set<br />

000 : 192.168.1.254<br />

1-254 : Static rotary<br />

300 : BootP<br />

400 : DHCP<br />

500 : PGM<br />

600 : PGM-DHCP