<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

Table 18:<br />

Module<br />

parameters<br />

A Defaultsettings<br />

XN-2AI-PT/NI-2/3 (2 byte parameter per channel)<br />

Byte Bit Parameter<br />

name<br />

0/2 0 mains<br />

suppression<br />

1 value<br />

representation<br />

Value<br />

– Meaning<br />

0 = 50 Hz A<br />

0 = 60 Hz<br />

0 = Integer (15 bit + sign) A<br />

1 = 12 bit (left justified)<br />

2 diagnosis 0 = release A<br />

1 = block<br />

3 channel 0 = activate A<br />

7 to<br />

4<br />

1 = deactivate<br />

element 0000 = Pt100, -200...850 °C A<br />

0001 = Pt100, -200...150 °C<br />

0010 = Ni100, -60...250 °C<br />

0011 = Ni100, -60...150 °C<br />

0100 = Pt200, -200...850 °C<br />

0101 = Pt200, -200...150 °C<br />

0110 = Pt500, -200...850 °C<br />

0111 = Pt500, -200...150 °C<br />

1000 = Pt1000, -200...850 °C<br />

1001 = Pt1000, -200...150 °C<br />

1010 = Ni1000, -60...250 °C<br />

1011 = Ni1000, -60...150 °C<br />

1100 = resistance, 0...100 Ω<br />

1101 = resistance, 0...200 Ω<br />

1110 = resistance, 0...400 Ω<br />

1111 = resistance, 0...1000 Ω<br />

1/3 0 measurement<br />

mode<br />

0 = 2-wire A<br />

1 = 3-wire<br />