<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />
Table 18:<br />
Module<br />
parameters<br />
A Defaultsettings<br />
XN-2AI-PT/NI-2/3 (2 byte parameter per channel)<br />
Byte Bit Parameter<br />
name<br />
0/2 0 mains<br />
suppression<br />
1 value<br />
representation<br />
Value<br />
– Meaning<br />
0 = 50 Hz A<br />
0 = 60 Hz<br />
0 = Integer (15 bit + sign) A<br />
1 = 12 bit (left justified)<br />
2 diagnosis 0 = release A<br />
1 = block<br />
3 channel 0 = activate A<br />
7 to<br />
4<br />
1 = deactivate<br />
element 0000 = Pt100, -200...850 °C A<br />
0001 = Pt100, -200...150 °C<br />
0010 = Ni100, -60...250 °C<br />
0011 = Ni100, -60...150 °C<br />
0100 = Pt200, -200...850 °C<br />
0101 = Pt200, -200...150 °C<br />
0110 = Pt500, -200...850 °C<br />
0111 = Pt500, -200...150 °C<br />
1000 = Pt1000, -200...850 °C<br />
1001 = Pt1000, -200...150 °C<br />
1010 = Ni1000, -60...250 °C<br />
1011 = Ni1000, -60...150 °C<br />
1100 = resistance, 0...100 Ω<br />
1101 = resistance, 0...200 Ω<br />
1110 = resistance, 0...400 Ω<br />
1111 = resistance, 0...1000 Ω<br />
1/3 0 measurement<br />
mode<br />
0 = 2-wire A<br />
1 = 3-wire<br />
M001973-01, 07/2007 83