<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 9 Appendix<br />

Table 66:<br />

Meaning of the<br />

data bits (process<br />

output)<br />

A Unlike the physical<br />

digital output<br />

DO1,<br />

output DO2 is only a<br />

data value that is indicated<br />

with the<br />

data bit STS_DO2<br />

of the process<br />

input.<br />

Control bit Explanations<br />

MODE_DO2 Only valid if LOAD_DO_PARAM: “0“ → “1“.<br />

The virtual A output DO2 can show the status of the<br />

data bit SET_DO2 or comparison results if<br />

CTRL_DO2 = 1.<br />

MODE_DO2 defines which function DO2 is to<br />

accept:<br />

– 00: The output DO2 shows the status of the<br />

control bit SET_DO2.<br />

This must be released with CTRL_DO2 = 1.<br />

– 01:Output DO2 indicates:<br />

Counter status ≥ reference value 2<br />

– 10:Output DO2 indicates:<br />

Counter status ≤ reference value 2<br />

– 11:Output DO2 indicates:<br />

Counter status = reference value 2<br />

A pulse is generated for indicating equal values.<br />

The pulse duration is defined by byte 2 of this<br />

process output.s<br />

MODE_DO1 Only valid if LOAD_DO_PARAM: “0“ → “1“.<br />

The physical output DO1 can show the status of the<br />

data bit SET_DO1 or comparison results if<br />

CTRL_DO1 = 1.<br />

MODE_DO1 defines which function DO1 is to<br />

accept:<br />

– 00: The output DO1 shows the status of the<br />

control bit SET_DO1. This must be released with<br />

CTRL_DO1 = 1.<br />

– 01:Output DO1 indicates:<br />

Counter status ≥ reference value 1<br />

– 10:Output DO1 indicates:<br />

Counter status ≤ reference value 1<br />

– 11:Output DO1 indicates:<br />

Counter status = reference value 1<br />

A pulse is generated for indicating equal values.<br />

The pulse duration is defined by byte 2 of this<br />

process output.<br />

M001973-01, 07/2007 185