<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 9 Appendix<br />

Control bit Explanations<br />

SET_DO1 If CTRL_DO1 = 1 and the physical output DO1 is<br />

configured for indicating the value SET_DO1, DO1<br />

can be set and reset directly with SET_DO1.<br />

DO1 can be set for this function via the process<br />

output<br />

(MODE_DO1 = 00 and LOAD_DO_PARAM 0 → 1).<br />

The output DO1 can also be set before commissioning<br />

via the separate parameter data. The default<br />

setting for DO1 is to display the value of SET_DO1.<br />

RES_STS 0 →1 Initiate resetting of status bits. The<br />

STS_UFLW, STS_OFLW and STS_CMP1 (process<br />

input) status bits are reset. Bit RES_STS_A = 1<br />

(process input) acknowledges that the reset<br />

command has been received. RES_STS can now be<br />

reset to 0.<br />

SW_GATE 0 → 1: Measuring is started (software release).<br />

1 → 0: Measuring is stopped.<br />

LOAD_DO_<br />

PARAM<br />

LOAD_<br />

INTTIME<br />

Parameter setting of the physical output DO1<br />

0 → 1: DO1 can indicate the status of different data<br />

bits as a signal. The current telegram (byte 0) determines<br />

the data bits to which DO1 is to refer.<br />

Parameter setting of the Integration time<br />

0 → 1: Bytes 0 to 1 of this process output represent<br />

a factor for forming the Integration time for<br />

frequency measurement and for determining the<br />

rotational speed. The integration time can be<br />

adjusted between 10 ms and 10 s in 10 ms increments<br />

and is produced by multiplying the factor x 10<br />

ms.<br />

With period duration measurement, this factor<br />

determines the number of periods measured in<br />

order to calculate a mean value.<br />

A factor 1 to 1000 (1hex to 3E8hex) is permissible.<br />