<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 6 Application example: Modbus TCP<br />

6.3.2 Reading-out the reference module list<br />

Figure 49:<br />

Reading out the<br />

reference module<br />

list<br />

Figure 50:<br />

Reference module<br />

list<br />

A Ident no. of<br />

module 0<br />

The reference module list is stored in the register area 0×2800 to<br />

0×2840. It can be read by using function code 03 "read multiple<br />

registers":<br />

Each module is clearly identified by a 4-byte ident-number. Bytes 3<br />

to 1 define module type, Byte 0 is reserved for manufacturer specific<br />

data.<br />

M001973-01, 07/2007 125<br />