<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 8 Guidelines for Electrical Installation<br />

8.3.5 Mounting Rails<br />

All mounting rails must be mounted onto the mounting plate with a<br />

low impedance, over a large surface area, and must be correctly<br />

earthed.<br />

Figure 73:<br />

Mounting options<br />

A TS 35<br />

B Mounting rail<br />

C Mounting plate<br />

Mount the mounting rails over a large surface area and with a low<br />

impedance to the support system using screws or rivets.<br />

Remove the isolating layer from all painted, anodized or isolated<br />

metal components at the connection point. Protect the connection<br />

point against corrosion (for example with grease; caution: use only<br />

suitable grease).<br />