<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 7 Guidelines for Station Planning<br />

When using a digital input module for 120/230 V AC, it should be<br />

ensured that a potential group is created in conjunction with the<br />

Power Feeding module XN-PF-120/230VAC-D.<br />

Attention<br />

It is not permitted to use the modules with 24 V DC and<br />

120/230 V AC field supply in a joint potential group.<br />

7.2.3 Protecting the Service Interface on the Gateway<br />

During operation, the cover protecting the service interface and the<br />

hexadecimal rotary coding-switches must remain closed due to<br />

EMC and ESD.<br />