<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 4 Technical Features<br />

Table 4:<br />

LED-displays<br />

LED Status Meaning Remedy<br />

IOs Off CPU not supplied. – Check the voltage<br />

supply at the gateway.<br />

Green Module bus is<br />

running,<br />

the configured<br />

module bus station<br />

corresponds to the<br />

physically connected<br />

station, communication<br />

is active.<br />

Green,<br />

flashing<br />

1 Hz<br />

Green,<br />

flashing<br />

4Hz<br />

Station is in the<br />

I/O-ASSISTANT<br />

Force Mode.<br />

Maximum number of<br />

modules at the<br />

gateway is exceeded.<br />

Red Controller is not<br />

ready, V CC level is not<br />

within the required<br />

range →<br />

possible reasons:<br />

– too many modules<br />

connected to the<br />

gateway<br />

– short circuit in<br />

connected module<br />

– hardware error in<br />

– gateway<br />

M001973-01, 07/2007 49<br />

-<br />

– Deactivate the<br />

I/O-ASSISTANT Force<br />

Mode.<br />

– Check the number of<br />

modules connected to<br />

the gateway, dismount<br />

modules<br />

– Check wiring at the<br />

gateway and the<br />

voltage supply.<br />

– Dismount modules<br />

– Replace the gateway.