<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

Table 12:<br />

Supported service<br />

numbers:<br />

Service response area<br />

2080h 2081h 2082h 2083h 2084h 2085h 20FFh<br />

service<br />

no.<br />

result service<br />

code<br />

After the execution of a request, the registers service-no., service<br />

code and index/addr in the response area contain a copy of the<br />

values in the request area.<br />

The register result shows whether the execution was successful or<br />

not.<br />

The register data-reg-count contains the number of data registers<br />

(0 to 122).<br />

The optional Data area can contain, depending on the service, the<br />

requested data.<br />

Supported service numbers:<br />

index/<br />

addr<br />

dataregcount<br />

optional data<br />

(0 to 122 registers)<br />

Note<br />

The service no. is thus used for a simple handshake on the application<br />

level. The application increases the service no. with every request.<br />

The service is blocked, until the service number in the request<br />

area matches the service number in the response area.<br />

Service code Meaning<br />

0×0000 no function<br />

0×0003 indirect reading of registers<br />

0×0010 indirect writing of registers<br />

M001973-01, 07/2007 77