<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

A Default<br />

settings<br />

Byte Bit Parameter<br />

name<br />

13 0/ 1 Signal evaluation<br />

(A,B)<br />

2 Sensor/ input<br />

filter (A)<br />

3 Sensor/ input<br />

filter (B)<br />

4 Sensor/ input<br />

filter (DI)<br />

Value<br />

– Meaning<br />

00 = pulse and direction A<br />

01 = rotary sensor: single<br />

10 = rotary sensor: double<br />

11 = rotary sensor: fourfold<br />

0 = 2,5 ms (200 kHz) A<br />

1 = 25 ms (20 kHz)<br />

0 = 2,5 ms (200 kHz) A<br />

1 = 25 ms (20 kHz)<br />

0 = 2,5 ms (200 kHz) A<br />

1 = 25 ms (20 kHz)<br />

5 Sensor (A) 0 = normal A<br />

1 = inverted<br />

7 Direction input<br />

(B)<br />

14 0 Group diagnostics<br />

4/ 5 Behavior CPU/<br />

master STOP<br />

0 = normal A<br />

1 = inverted<br />

0 = release A<br />

1 = block<br />

– 00 = switch off DO1 A<br />

– 01 = proceed with operating<br />

mode<br />

– 10 = DO1 switch to substitute<br />

value<br />

– 11 = DO1 hold last value<br />

M001973-01, 07/2007 91