<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

A ro = read only<br />

rw = read/write<br />

Address<br />

(hex.)<br />

0×1018 to<br />

0×101A<br />

Access<br />

A<br />

<strong>Description</strong><br />

ro group diagnostics of I/O-modules 0 to 32<br />

(1 bit per I/O-module)<br />

0×1020 ro watchdog, actual time [ms]<br />

0×1120 rw watchdog predefined time [ms]<br />

(default: 0)<br />

0×1121 rw watchdog reset register<br />

0×1130 rw modbus connection mode register<br />

0×1131 rw modbus connection time-out in seconds<br />

(default: 0 = never)<br />

0×113C to<br />

0×113D<br />

0×113E to<br />

0×113F<br />

0×2000 to<br />

0×207F<br />

0×2080 to<br />

0×20FF<br />

rw modbus parameter restore<br />

rw modbus parameter save<br />

rw service-object, request-area<br />

ro service-object, response-area<br />

0×2400 ro system voltage U SYS [mV]<br />

0×2401 ro load voltage U L [mV]<br />

0×2405 ro load current I L [A]<br />

0×27FE ro no. of entries in actual module list<br />

0×27FF rw no. of entries in reference module list<br />

0×2800 to<br />

0×2840<br />

0×2900 to<br />

0×29A0<br />

rw reference module list (32 × 4 bytes per<br />

module-ID)<br />

ro reserved<br />

M001973-01, 07/2007 61