<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 6 Application example: Modbus TCP<br />

6.5.1 Group diagnosis within the process input data:<br />

Figure 63:<br />

Group diagnosis<br />

in the process<br />

data<br />

A group diagnosis<br />

Table 58:<br />

Group diagnosis,<br />

byte 0,<br />

Value: 0×08<br />

Table 59:<br />

Group diagnosis,<br />

byte 1, value 0×02<br />

Group diagnosis message: 0×02 0×08<br />

Byte 0 (modules 0 to 7): 0×08<br />

→ Bits 3 is set, which means module 3 sends a diagnostic message:<br />

Bit 7 6 5 4 3 2 1 0<br />

Value 0 0 0 0 1 0 0 0<br />

Byte 1 (modules 8 to 15): 0×02<br />

→ Bit 1 is set, module 9 sends a diagnosis message.<br />

Bit 7 6 5 4 3 2 1 0<br />

Value 0 0 0 0 0 0 1 0<br />

146 M001973-01, 07/2007<br />