<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 6 Application example: Modbus TCP<br />

Figure 62:<br />

Parameterization<br />

of XN-1SSI<br />

A register-no.<br />

B register-value<br />

Thus, for setting the baudrate to "71000 Bit/s", bits 0 to 3, in byte 2<br />

in register 0×B121 have to be set. The value "0110 (0×06) =<br />

71000bps" has to be written into byte 2.<br />

The value 0×1906 is written in register 0×B121:<br />

Byte 2: 0×06 (change in parameters)<br />

Byte 3: 0×19 (default setting)<br />

A B<br />

144 M001973-01, 07/2007