<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 6 Application example: Modbus TCP<br />

Digital modules<br />

The input data of the digital modules occupy 1 register (register<br />

0×0009):<br />

Value: 0×02 0×05<br />

XN-2DI-24VDC-P<br />

→ 2 bits<br />

– register 0×0009:<br />

byte 0, bits 0 and 1 („0×01“: input 0 = bit 0 = 1)<br />

XN-4DI-24VDC-P<br />

→ 4 bits<br />

– register 0×0009:<br />

byte 0, bits 2 and 5 („0×04“: input 0 = bit 2 = 1)<br />

XN-4DI-24VDC-P<br />

→ 4bits<br />

– register 0×0009:<br />

byte 0, bits 6 and 7 („0×00“: input 0 and 1 = 0)<br />

byte 1, bits 0 and 1 („0×02“: input 3 = 1)<br />

M001973-01, 07/2007 133