<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 9 Appendix<br />

Designation Value Meaning<br />

STS_OFLW 0 A comparison of the register contents<br />

has produced the following result:<br />

(REG_SSI_POS) ≤<br />

(REG_UPPER_LIMIT)<br />

1 A comparison of the register contents<br />

has produced the following result:<br />

(REG_SSI_POS) ><br />

(REG_UPPER_LIMIT)<br />

ERR_SSI 0 SSI encoder signal present.<br />

1 SSI encoder signal faulty. (e.g. due to<br />

a cable break).<br />

SSI_DIAG 0 No enabled status signal is active<br />

(SSI_STSx = 0).<br />

1 At least one enabled status signal is<br />

active (SSI_STSx = 1).<br />

M001973-01, 07/2007 205