<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 9 Appendix<br />

Process output data - counter mode<br />

The process output data is the data that is output from the PLC via<br />

the gateway to the XN-1CNT-24VDC module.<br />

The XN-1CNT-24VDC module allows some parameters to be modified<br />

during operation.<br />

The other parameters must be changed prior to commissioning.<br />

Note<br />

The current count operation is stopped if parameters are changed<br />

during operation.<br />

Note<br />

The parameters modified via the process output data are not retentive.<br />

The commissioning after a power failure is based on the parameter<br />

data of the configuration tool or default configuration.<br />

The data is transferred in 8 byte format:<br />

Two control bytes contain the control functions for transferring<br />

the parameter values, for starting/stopping the measurement,<br />

for acknowledging errors and for resetting the status bit.<br />

Four bytes provide the parameter values for “Load direct“, “Load<br />

in preparation“, “Reference value 1“, “Reference value 2“ or<br />

“Behavior of the digital outputs“.<br />

182 M001973-01, 07/2007