<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

5.5.4 Register 0×113C and 0×113D:<br />

"Restore Modbus-connection parameter"<br />

Registers 0×113C and 0×113D serve for resetting the parameterregister<br />

0×1120 and 0×1130 to 0×113B to the default settings.<br />

For this purpose, write "0×6C6F" in register 0×113C. To activate the<br />

reset of the registers, write "0×6164" ("load") within 30 seconds in<br />

register 0×113D.<br />

Both registers can also be written with one single request using the<br />

function codes FC16 and FC23.<br />

The service resets the parameters without saving them. This can be<br />

achieved by using a following "save" service.<br />

5.5.5 Register 0×113E and 0×113F:<br />

"Save Modbus-connection parameters"<br />

Registers 0×113E and 0×113F are used for the non-volatile saving<br />

of parameters in registers 0×1120 and 0×1130 to 0×113B.<br />

For this purpose, write "0×7361" in register 0×113E. To activate the<br />

saving of the registers, write "0×7665" ("save") within 30 seconds in<br />

register 0×113F.<br />

Both registers can also be written with one single request using the<br />

function codes FC16 and FC23.<br />

M001973-01, 07/2007 75