<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 8 Guidelines for Electrical Installation<br />

Note<br />

Should it not be possible to ground the shield on both sides due to<br />

switching arrangements or device specific reasons, then it is possible<br />

to route the second cable shield side to the local reference potential<br />

via a capacitor (short connection distances). If necessary, a<br />

varistor or resistor can be connected parallel to the capacitor, to<br />

prevent disruptive discharges when interference pulses occur.<br />

A further possibility is a double-shielded cable (galvanically separated),<br />

whereby the innermost shield is connected on one side and the<br />

outermost shield is connected on both sides.<br />

M001973-01, 07/2007 171