<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 6 Application example: Modbus TCP<br />

6.3.6 Evaluation of the packed process data (inputs)<br />

Figure 56:<br />

Packed process<br />

input data<br />

Intelligent modules<br />

The input data of the intelligent modules occupy 10 registers<br />

(register 0×0000 to 0×0008):<br />

XN-2AI-I(0/4...20MA)<br />

→ 2 registers (0×0000 and 0×0001)<br />

– channel 0: not used, measurement range 0 to 20 mA<br />

register 0×0000: 0×00 0×00<br />

– channel 1: not used, measurement range 0 to 20 mA<br />

register 0×0001: 0×00 0×00<br />

→ The module shows the lower measurement limit when<br />

the channel is not used.<br />

XN-2AI-THERMO-PI<br />

→ 2 registers (0×0002 and 0×0003)<br />

– channel 0: thermo element type K connected.<br />

register 0×0002: 0×00 0×D1<br />

→ The module shows a measured temperature of<br />

0×D1 ≈ 21,0 °C at channel 0.<br />

– channel 1: no thermo element connected<br />

register 0×0003: 0×F5 0×74<br />

→ As the channel is not used, the module shows the<br />

minimum value at channel 1 (- 270 °C).<br />