<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

5.6 The Service-Object<br />

The service-object is used to execute one-time or acyclic services.<br />

It is an acknowledge service which may serve, for example, to<br />

parameterize an I/O-module.<br />

2000h 2080h 20FFh<br />

service request area service response area<br />

The service request area allows write access, the service response<br />

area only read access.<br />

Service request area<br />

2000h 2001h 2002h 2003h 2004h 2005h 207Fh<br />

service<br />

no.<br />

reserve<br />

d<br />

service<br />

code<br />

index/<br />

addr<br />

dataregcount<br />

optional data<br />

(0 to122 registers)<br />

The register service no. in the request area can contain a user<br />

defined value which is deleted after the execution of the service.<br />

The register service code specifies which service is requested.<br />

The register index/addr is optional and the meaning depends on<br />

the particular service.<br />

The register data-reg-count contains, depending on the service,<br />

the number (0 to 122) of the transferred or of the requested data<br />

registers.<br />

Depending on the service, the optional data area can contain additional<br />

parameters and/or other data to be written.<br />

76 M001973-01, 07/2007