<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 9 Appendix<br />

Control bit Explanations<br />

LOAD_<br />

UPLIMIT<br />

LOAD_<br />

LOPLIMIT<br />

Parameter setting of the upper measuring limit<br />

0 → 1: The value in bytes 0 to 3 is accepted directly<br />

as the new upper measuring limit. LOAD_UPLIMT:<br />

1 to 200 000 000 x 10 -3 Hz<br />

1 to 25 000 000 x 10 -3 rpm<br />

1 to 100 000 000 ms<br />

Parameter setting of the lower measuring limit<br />

0 A 1: The value in bytes 0 to 3 is accepted directly<br />

as the new lower measuring limit.<br />

LOAD_LOLIMIT:<br />

0 to 199 999 999 x10 -3 Hz<br />

0 to 24 999 999 x 10 -3 rpm<br />

0 to 99 999 999 ms<br />

MODE_DO1 MODE_DO1 is only valid if LOAD_DO_PARAM:<br />

0 → 1. The physical output DO1 can show the status<br />

of the data bit SET_DO1 or comparison results if<br />

CTRL_DO1 = 1.<br />

MODE_DO1 defines which function DO1 is to<br />

accept:<br />

– 00: The output DO1 indicates the status of the<br />

control bit SET_DO1.<br />

– 01: The output DO1 indicates a measurement<br />

outside of the limits, i.e. above the upper<br />

measuring limit or below the lower measuring limit.<br />

STS_OFLW = 1 or STS_UFLW = 1 (process input).<br />

– 10: Output DO1 indicates a value below the lower<br />

measuring limit. STS_UFLW = 1 (process input)<br />

– 11:Output DO1 indicates a value above the upper<br />

measuring limit. STS_OFLW = 1 (process input)<br />

M001973-01, 07/2007 193