<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

A Default<br />

settings<br />

Byte Bit Parameter<br />

name<br />

Value<br />

– Meaning<br />

12 2/ 3 Function DO1 00 = output A<br />

01 = outside of limit<br />

10 = below lower limit<br />

11 = above upper limit<br />

13 0/ 1 Signal evaluation<br />

(A,B)<br />

2 Sensor/<br />

input filter (A)<br />

3 Sensor/<br />

input filter (B)<br />

4 Sensor/input<br />

filter (DI)<br />

00 = pulse and directionA<br />

01 = rotary sensor: single<br />

0 = 2,5 ms (200 kHz) A<br />

1 = 25 ms (20 kHz)<br />

0 = 2,5 ms (200 kHz) A<br />

1 = 25 ms (20 kHz)<br />

0 = 2,5 ms (200 kHz) A<br />

1 = 25 ms (20 kHz)<br />

5 Sensor (A) 0 = normal A<br />

1 = inverted<br />

7 Direction input<br />

(B)<br />

14 0 Group<br />

diagnostics<br />

4/ 5 Behaviour CPU/<br />

master STOP<br />

0 = normal A<br />

1 = inverted<br />

0 = release A<br />

1 = block<br />

00 = turn off DO1 A<br />

10 = proceed with operating mode<br />

01 = DO1 switch to substitute value<br />

11 = DO1 hold last value<br />