<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 7 Guidelines for Station Planning<br />
Figure 66:<br />
Power supply of<br />
the station<br />
+ –<br />
Field<br />
supply<br />
Gateway<br />
10/100 MBit<br />
+ - + -<br />
+ –<br />
System<br />
sypply<br />
2 DI 2 DO 2 DI 2 DO 2 DI 1AO BR AI 2 DI NO<br />
11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21<br />
12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22<br />
13 23 13 23 13 23 13 23 13 23 13 23 13 23 13 23 13 23 13 23<br />
14<br />
24<br />
It must be ensured that the same ground potential and ground<br />
connections are used. If different ground potentials or ground<br />
connections are used, compensating currents flow via the module<br />
bus, which can lead to the destruction of the Bus Refreshing<br />
module.<br />
All Bus Refreshing modules are connected to one another via the<br />
same ground potential.<br />
The power to the module bus is supplied via the connections 11 and<br />
21 on the base module.<br />
Attention<br />
In order to comply with radiation limit values in accordance with<br />
EN 55 011/ 2 000, the supply lines of the XN-BR-24VDC-D module<br />
for supplying the gateway with power are to be fed through a ferrite<br />
ring. This is to be placed immediately next to the connection terminals.<br />
From there on, it is not permitted to make connections to further<br />
devices.<br />
156 M001973-01, 07/2007<br />
24<br />
14 24 14 24 14 24 14 24 14 24<br />
SBBC-B<br />
– +<br />
Field supply<br />
TS