<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 7 Guidelines for Station Planning<br />

Figure 66:<br />

Power supply of<br />

the station<br />

+ –<br />

Field<br />

supply<br />

Gateway<br />

10/100 MBit<br />

+ - + -<br />

+ –<br />

System<br />

sypply<br />

2 DI 2 DO 2 DI 2 DO 2 DI 1AO BR AI 2 DI NO<br />

11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21<br />

12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22<br />

13 23 13 23 13 23 13 23 13 23 13 23 13 23 13 23 13 23 13 23<br />

14<br />

24<br />

It must be ensured that the same ground potential and ground<br />

connections are used. If different ground potentials or ground<br />

connections are used, compensating currents flow via the module<br />

bus, which can lead to the destruction of the Bus Refreshing<br />

module.<br />

All Bus Refreshing modules are connected to one another via the<br />

same ground potential.<br />

The power to the module bus is supplied via the connections 11 and<br />

21 on the base module.<br />

Attention<br />

In order to comply with radiation limit values in accordance with<br />

EN 55 011/ 2 000, the supply lines of the XN-BR-24VDC-D module<br />

for supplying the gateway with power are to be fed through a ferrite<br />

ring. This is to be placed immediately next to the connection terminals.<br />

From there on, it is not permitted to make connections to further<br />

devices.<br />

156 M001973-01, 07/2007<br />

24<br />

14 24 14 24 14 24 14 24 14 24<br />

SBBC-B<br />

– +<br />

Field supply<br />

TS