06.03.2013 Views

Product Description XI/ON - Eaton Automation

Product Description XI/ON - Eaton Automation

Product Description XI/ON - Eaton Automation

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 5 Implementation of Modbus TCP<br />

5.8.2 Analog output modules<br />

Table 21:<br />

Module<br />

parameters<br />

A Defaultsettings<br />

XN-1AO-I(0/4...20MA) (3 Byte pro Kanal)<br />

Byte Bit Parameter<br />

name<br />

Value<br />

– Meaning<br />

0 0 current mode 0 = 0...20 mA A<br />

1 value<br />

representation<br />

2 to<br />

7<br />

reserved<br />

1 substitute value<br />

low byte<br />

2 substitute value<br />

high byte<br />

1 = 4...20 mA<br />

0 = Integer (15 bit + sign) A<br />

1 = 12 bit (left justified)<br />

The substitute value will be transmitted<br />

if the respective parameters<br />

of the gateway have been set to<br />

"output substitute value".<br />

86 M001973-01, 07/2007

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!