<strong>XI</strong>/<strong>ON</strong>: Gateways for Modbus TCP 7 Guidelines for Station Planning<br />
Figure 71:<br />
Using the C-rail as<br />
protective earth<br />
and for the power<br />
supply with relay<br />
modules<br />
Attention<br />
When relay modules are planned and the C-rail is used for a common<br />
voltage supply, a further power distribution module must be<br />
used for the potential isolation to the following modules. The C-rail<br />
can only again be used as a PE following potential isolation.<br />
PE<br />
terminal<br />
10/100 MBit<br />
+ - + -<br />
Cross-connecting relay module roots is achieved by the use of<br />
jumpers. The corresponding connection diagrams can be found in<br />
the following manual:<br />
M001736<br />
<strong>Product</strong> <strong>Description</strong> <strong>XI</strong>/<strong>ON</strong><br />
Digital I/O-Modules, Supply Modules<br />
7.2.5 Direct Wiring of Relay Modules<br />
PF<br />
11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21<br />
12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22<br />
13 23 13 23 13 23 13 23 13 23 13 23 13 23 13 23 13 23 13 23<br />
C-rail (PE)<br />
C-rail (24 V DC)<br />
14 24 14 24<br />
14 24 14 24 14 24 14 24 14 24<br />
SBBC<br />
As well as the options mentioned above, relay modules can be wired<br />
directly. In this case, base modules without C-rail connections<br />
should be chosen to guarantee the potential isolation to the<br />
adjoining modules.<br />