02.07.2013 Views

Electrical Power Systems

Electrical Power Systems

Electrical Power Systems

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

120 <strong>Electrical</strong> <strong>Power</strong> <strong>Systems</strong><br />

L<br />

NMHG<br />

2166 10 25 33 25<br />

\ tS = 1<br />

76 2 2<br />

. ´ + . ´<br />

-<br />

( . )<br />

\ t S = 1.08, \ t R = 0.92 Ans.<br />

I KJ<br />

O<br />

QP<br />

1 1/2<br />

-<br />

Example 5.13: A 12.66 kV line is fed through an 11/132 kV transformer from a constant 11 kV<br />

supply. At the load end of the line the voltage is reduced by another transformer of nominal ratio<br />

132/11 kV. The total impedance of the line and transformers at 132 kV is (25 + j66)W. Both<br />

transformers are equipped with tap-changing facilities which are arranged so that the product<br />

of the two off-nominal settings is unity. If the load on the system is 100 MW at 0.9 pf lagging,<br />

calculate the settings of the tap-changers required to maintain the voltage of the load busbar at<br />

11 kV.<br />

Solution: As the voltage drop is to be completely componsated,<br />

Using eqn. (5.43)<br />

|V 1 | = |V 2 | = 132<br />

t S =<br />

\ t S =<br />

L<br />

NM<br />

<br />

HG<br />

3<br />

| V2|<br />

PR + QX<br />

1 -<br />

| V | | V|| V|<br />

1 1 2<br />

KV = 76.2 KV<br />

I<br />

KJ<br />

O<br />

QP<br />

-1<br />

1/ 2<br />

P = 1<br />

× 100 × 0.9 = 30 MW<br />

3<br />

Q = 1<br />

× 100 × 0.435 = 14.53 MVAr., R = 25 W, X = 66 W<br />

3<br />

L<br />

NM<br />

<br />

HG<br />

30 ´ 25 + 14.53 ´ 66<br />

1× 1 –<br />

\ t S = 1.19; t R = 0.84.<br />

(76.2) 2<br />

I<br />

KJ<br />

O<br />

QP<br />

-1 12 /<br />

There settings are large for the normal range of tap-changing transformers. It would be<br />

necessary, in this system, to inject vars at the load end of the line to maintain the voltage at the<br />

required value.<br />

5.5.2 Booster Transformers or Regulating Transformers<br />

Regulating transformers also known as booster transformers. These are used to change the<br />

voltage magnitude and phase angle at an intermediate point in a line rather than at the ends<br />

as with tap-changing transformers or the system may not warrant the expense of tap-changing.<br />

A. Voltage Magnitude Control<br />

igure 5.29 shows the connection of a booster transformer for phase a. The secondary of the<br />

exciting transformer is tapped and the voltage obtained from it is applied to the primary of the<br />

series transformer. The corresponding secondary voltage of the series transformer is added to<br />

the input voltage. Therefore, the output voltage is

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!