02.07.2013 Views

Electrical Power Systems

Electrical Power Systems

Electrical Power Systems

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

334 <strong>Electrical</strong> <strong>Power</strong> <strong>Systems</strong><br />

New load in area-1 and area-2,<br />

Generation in area-1 and area-2,<br />

LOAD 1 = 20,000 – 1000 + 17.392 = 19017.392 MW<br />

LOAD 2 = 40,000 + 36.616 = 40036.616 MW<br />

PG 1 = 19000 – 305.13 = 18694.87 MW<br />

PG 2 = 41000 – 640.78 = 40359.22 MW<br />

P tie,21 = LOAD 1 – PG 1 = 19017.392 – 18694.87<br />

\ P tie,21 = 322.522 MW.<br />

(b) With supplementary control<br />

(i) Loss of 1000 MW load in area-1<br />

Area-1 has a generating capacity of 4000 MW on supplementary control and this will reduce<br />

generation so as to bring ACE 1 to zero. Similary, area-2 generation on supplementary control<br />

will keep ACE 2 at zero.<br />

ACE 1 = B 1 Df + DP tie,12 = 0<br />

ACE 2 = B 2 Df – DP tie,12 = 0<br />

Hence, Df = 0.0, DP tie,12 = 0.0<br />

Area-1 generation and load are reduced by 1000 MW. There is no steady-state change in<br />

area-2 generation and load, or the tie flow.<br />

(ii) Loss of 500 MW generation carrying part of spinning reserve in area-1:<br />

Spinning reserve lost with generation loss is<br />

500 ´ 1000<br />

= 166.67 MW<br />

b4000 - 1000g<br />

Spinning reserve remaining is (1000 – 166.67) = 833.33 MW. This is sufficient to make up<br />

500 MW. Hence, the generation and load in the two areas are restored to their pre-disturbance<br />

values. There are no changes in system frequency or tie-line power flow.<br />

12.19 GENERATION RATE CONSTRAINT (GRC)<br />

In establishing AGC signals, it should be recognized that there is a limit to the rate at which<br />

generating unit outputs can be changed. This is particularly true for thermal units where<br />

mechanical and thermal stresses are the limiting factors. igure 12.24 shows the flow chart for<br />

incorporating the effect of GRC in the matrix differential equation X • = AX + BU + Gp for<br />

obtaining the system response at various states. At each time interval of Dt seconds for<br />

integration, the generation rate is checked for its magnitude and sign; that is for the K-th<br />

•<br />

interval, if the generation rate | DP gi,k | are less than or equal to a specified maximum rate<br />

(say r), the corresponding generation changes DPgi,k is not altered. In case the generation rate<br />

exceeds the maximum specified rate r, the generation change is constrained through the<br />

relationship<br />

DP gi,k = DP gi,k-1 + r.Dt ...(12.49)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!