Automatic Generation Control: Conventional Scenario 321<br />

ig. 12.14: Multi-unit isolated power system.<br />

It has already mentioned in the previous section that the supplementary generation control<br />

action is much slower than the primary speed control action. As such it comes into action after<br />

the primary speed control has stabilized the system frequency. or isolated system, function of<br />

AGC is to restore system frequency to the specified nominal value and this is accomplished by<br />

adding a reset or integral control. This is shown in ig. 12.15.<br />

ig. 12.15: Structure of integral controller.<br />

Note that a1, a2, ..., an are the participation factor and a1 + a2 + ... + an = 1.0. At steady state,<br />

output of each generating unit can be given as:<br />

DPg1ss = a1 .DPL DPg2ss = a2 . DPL . .<br />

. . ...(12.21)<br />

. .<br />

DPgnss = anDPL Readers may easily verify that through computer simulation.