146 <strong>Electrical</strong> <strong>Power</strong> <strong>Systems</strong><br />

6.7. A three phase transmission line has A = D = 098 . 15 . ° , B = 755 . 80°<br />

and C = 4 × 10 –4 91° . If an<br />

impedance (2.64 + j42.3) ohms is connected in series with the line at the sending end, determine<br />

the new values of ABCD constants.<br />

Ans. Ao = 0963 . 153 . ° ; Bo = 116. 8 82. 8°<br />

ohms<br />

–4<br />

Co = 4 10 90<br />

´ °<br />

; Do = 098 . 15 . °<br />

6.8. A three phase, 50 Hz, 100 km transmission line has resistance 0.1 ohms/km, inductance<br />

111.7 mH/km and capacitance 0.9954 × 10 –2 m/ph per km. The line is delivering 20 MW at a 0.8<br />

power factor lagging and 66 kV to a balanced load. Determine the efficiency and regulation. Use<br />

nominal p method.<br />

Ans. h = 93.5%, VR = 17.47%<br />

6.9. A 132 kV, 50 Hz transmission line has the following generalised constants, A = D = 0.9696 049 . ° ,<br />

-4<br />

B = 52. 88 74. 79°<br />

ohms and C = 1177 . ´ 10 90. 15°<br />

mho. It is supplying a load of 125 MVA, 0.9<br />

power factor lagging at 132 kV. Calculate the sending end voltage and current.<br />

Ans. VS = 166.1 kV, IS = 554 Amp<br />

6.10. A three phase transmission line delivers a load of 5 MW at 0.8 power factor lagging. Resistance of<br />

each conductor is 0.5 W/km. Receiving end voltage is 33 kV. If the line loss is not to exceed 10%,<br />

determine the length of the line<br />

Ans. 27.9 km.<br />

6.11. The ABCD parameters of two transmission lines are A1 , B1 , C1 , D1 and A2 , B2 , C2 , D2 . ind the<br />

overall ABCD parameters when (i) the two networks are connected in series (ii) in parallel.<br />

6.12. Two overhead lines are connected in parallel to supply a load of 10 MW at 0.8 power factor lagging<br />

at 30 kV. The resistance and reactance of one line (A) are 5.5 W and 13.5 W respectively and for line<br />

(B) are 6 ohm and 11 ohm respectively, calculate (a) the KVA supplied by each line and (b) power<br />

supplied by each line<br />

Ans. (a) 5790, 6730 (b) 4415 kW, 5585 kW.<br />

6.13. A long transmission line has the following generalised constants: A = D = 092 . 53 . ° ; B = 65. 3 81°<br />

ohm. Two identical transformers, each of series impedance 100 70° ohms and admittance<br />

- 4<br />

2 ´ 10 - 75°<br />

mho are connected at the two ends of the line. Determine new values of generalised<br />

constants.<br />

Ans. Ao = Do = 0843 . 26 . 38°<br />

, Bo = 249. 3 76. 85°<br />

ohm<br />

–4<br />

Co = 34. 38 10 50. 9<br />

´ °mho