\<br />

T p = 32<br />

3 sec.<br />

Automatic Generation Control: Conventional Scenario 319<br />

(b) With DP g = 0 (no speed governing), the block diagram of ig. 12.10 with system parameters<br />

can be given as<br />

where K p = 1<br />

D<br />

The load change is<br />

= 160<br />

3<br />

T p = 32<br />

3 sec.<br />

DP L = 16 MW = 16<br />

1600<br />

Hz/pu MW.<br />

= 0.01 pu MW.<br />

or a step decrease in load by 0.01 pu, Laplace transform of the change in load is<br />

rom the block diagram<br />

\<br />

DPL (s) = 001 .<br />

S<br />

I <br />

HG KJ HG<br />

D f(s) = -001<br />

.<br />

S<br />

K<br />

p<br />

1 + ST<br />

p<br />

I<br />

KJ<br />

D f(t) = – 0.01 K p e – t/Tp + 0.01 K p<br />

\ Df(t) = 001 160<br />

. ´ – 001<br />

3<br />

160<br />

. ´ e<br />

3<br />

\<br />

Df(t) = 16<br />

3 1<br />

. 3 / 32<br />

- -<br />

e t<br />

ig. 12.13 shows the frequency response.<br />

– t/(32/3)<br />

e j Ans.<br />

\ D f ss = 0.533 Hz Ans.