ig. 10.9: Two conductors open.<br />

Unbalanced ault Analysis 257<br />

rom ig. 10.9, we can write<br />

V aa¢ = 0 ...(10.43)<br />

I b = I c = 0 ...(10.44)<br />

In terms of symmetrical components, we can write<br />

V aa¢1 + V aa¢2 + V aa¢0 = 0 ...(10.45)<br />

Ia1 = Ia2 = Ia0 = 1<br />

3 Ia ...(10.46)<br />

Equations (10.45) and (10.46) suggest a series connection of sequence network as shown in<br />

ig. 10.10.<br />

ig. 10.10: Sequence network for two conductors open.<br />

Example 10.1: or the system of example 9.5, the single line diagram is redrawn–in ig. 10.11.<br />

The positive, negative and zero sequence networks of the system have already been drawn in<br />

igs. 9.10(a), 9.10(b) and 9.10(c). Before the occurrence of a solid L-G fault at line g, the motors<br />

were loaded. If the prefault current is neglected, calculate the fault current and subtransient<br />

currents in all parts of the system.<br />

ig. 10.11: Single-line diagram the system of Example 10.1.