Automatic Generation Control: Conventional Scenario 331<br />

ig. 12.22 shows the dynamic responses for Df1, Df2, DPtie,12, DPg1 and DPg2 with and without<br />

considering integral controller. ollowing parameters were used for plotting ig. 12.22,<br />

R1 = R2 = 2.40 Hz/pu MW, Kp1 = Kp2 = 120 Hz/pu MW, Tp1 = Tp2 = 20 secs, Tg1 = Tg2 = 0.08 sec,<br />

Tt1 = Tt2 = 0.30 sec, T12 = 0.0866,<br />

a12 = – 1.0, DPL1 = 0.01 pu MW<br />

DPL2 = 0.0, KI1 = KI2 = 0.67.<br />

rom ig. 12.22, it is seen that with integral control action D f1 , D f2 and D Ptie,12 are setting<br />

to zero for a step load disturbance in area-1. Note that without integral control, load increase<br />

in area-1 is equally shared by both the units, i.e. DPg1 = DPg2 = 0.50 DPL1 = 0.005 pu MW. With<br />

integral control action DPg1 = DPL1 = 0.01 pu MW and DPg2 = 0.0.<br />