as:<br />

\ |V S| = 145.13 kV.<br />

\ Sending end line-to-line voltage<br />

Voltage regulation =<br />

Characteristics and Performance of Transmission Lines 133<br />

|V S| L–L = 3 × 145.13 = 251.37 kV<br />

25137 . - 220<br />

220<br />

Per phase real power loss in the line<br />

Per phase receiving end power<br />

= 14.26%<br />

P Loss = |I| 2 R = (787.4) 2 × 9 × 10 –6 MW = 5.58 MW.<br />

P R = 300<br />

3<br />

\ Per phase sending end power<br />

Transmission line efficiency is<br />

´ 08 . = 80 MW<br />

P S = (80 + 5.58) = 85.58 MW.<br />

R<br />

h = P<br />

P<br />

(b) 3|V R ||I R | = 300<br />

\ |V R| = 220 kV<br />

S<br />

= 80<br />

85. 58<br />

\ |I R| = 787.4 Amp<br />

= 93.47%.<br />

Load is at 0.8 power factor leading. or leading power factor load, eqn. (6.6) can be written<br />

|V S| = |V R|+ |I| (R cos d R – X sin d R)<br />

\ |V S| = 127 + 787.4 (9 × 0.8 – 26.39 × 0.6) = 120.2 kV<br />

\ |V S| L–L = 3 × 120.2 = 208.2 kV<br />

Voltage regulation =<br />

208. 2 - 220<br />

220<br />

= –5.36%<br />

Per phase real power loss = (787.4) 2 × 9 × 10 –6 = 5.58 MW<br />

Per phase receiving end power,<br />

P R = 300<br />

3<br />

Per phase sending end power,<br />

Transmission line efficiency<br />

´ 08 . = 80 MW<br />

P S = (80 + 5.58) = 85.58 MW<br />

R<br />

h = P<br />

P<br />

S<br />

= 80<br />

85. 58<br />

= 93.47%