212 <strong>Electrical</strong> <strong>Power</strong> <strong>Systems</strong><br />

In ig. 8.19, we excite the passive Thevenin network with – º<br />

V r is in series with Z f .<br />

Now<br />

DV = ZBUS Cf ...(8.5)<br />

Where ZBUS is the bus impedance matrix of the passive Thevenin network and is given by<br />

Z BUS =<br />

L<br />

NM<br />

Z Z ..... Z<br />

Z21 Z22 ..... Z<br />

M M M M<br />

Z Z ..... Z<br />

11 12 1n<br />

nn<br />

n1 n2 nn<br />

O<br />

QP<br />

...(8.6)<br />

and C f is bus current injection vector. The network is injected with current –I f only at the<br />

r-th bus, we have<br />

C f =<br />

L<br />

NM<br />

0<br />

0<br />

M<br />

I<br />

M<br />

0<br />

= -I<br />

rf f<br />

rom equations (8.5) and (8.7), we obtain,<br />

DV r = –Z rr I f<br />

The voltage at the r-th bus under fault is<br />

Also<br />

ig. 8.19: Thevenin network of ig. 8.18 with<br />

–V<br />

º<br />

r<br />

is in series with Zf .<br />

O<br />

QP<br />

...(8.7)<br />

...(8.8)<br />

Vrf = V + D V = V – Z I<br />

...(8.9)<br />

r º<br />

V rf = Z f I f<br />

r r º<br />

rr f<br />

...(8.10)