390 <strong>Electrical</strong> <strong>Power</strong> <strong>Systems</strong><br />

ig. 15.9: Wind force on conductor without ice.<br />

ig. 15.10: Wind force on conductor covered with ice.<br />

The projected area per meter length of the conductor with no ice is<br />

S ni = A ni.l ...(15.75)<br />

where<br />

S ni = projected area of conductor covered without ice in square meter per meter<br />

length.<br />

A ni = cross-sectional area of conductor covered without ice in square meter.<br />

l = length of conductor (meter)<br />

or 1-meter length of conductor with no ice<br />

Sni = dc 100 1 ´ m2 /m ...(15.76)<br />

with ice covered<br />

Swi = Awil ...(15.77)<br />

where<br />

Swi = projected area of conductor covered with ice in square meter per meter<br />

length.<br />

Awi = cross-sectioral area of conductor covered with ice in square meter.<br />

l = length of conductor (meter)<br />

or 1-meter length of conductor,<br />

bdc + 2tig<br />

Swi = ´ 1 m<br />

100<br />

2 /m ...(15.78)<br />

The horizontal force exerted on the line as a result of the pressure of wind without ice (ig.<br />

15.9) is<br />

= S ni.P ...(15.79)