Unbalanced ault Analysis 261<br />

Example 10.3: or example 10.2, assume that the Rn = 0. ind the fault current in each phase<br />

and voltage of the healthy phase for a double-line-to ground fault on terminals of the generator.<br />

Solution: Using eqn. (10.36)<br />

I a1 =<br />

\ I a1 =<br />

\ I a1 = – j16.56 pu<br />

Z<br />

1<br />

+ (+3 )<br />

Ea<br />

Z2 Z0 Zf<br />

Z + Z +3Z<br />

2 0 f<br />

10 .<br />

j0.025 ´ j0.04<br />

j0.045<br />

+<br />

j0.025 + j0.04<br />

Va1 = Va2 = Va0 = Ea – Ia1 Z1 = 1 – (–j16.56) ( j0.045)<br />

= 0.2548 pu.<br />

Ia2 = – Va2<br />

=<br />

Z2<br />

– 0.2548<br />

= j10.192 pu<br />

j0.025<br />

Ia0 = – Va0<br />

=<br />

Z0<br />

– 0.2548<br />

= j6.37 pu.<br />

j0.04<br />

Now<br />

Ib = b2 Ia1 + bIa2 + Ia0 \<br />

Ib = (– 0.5 – j0.866) (– j16.56) + (– 0.5 + j0.866) ( j10.192) + j6.37<br />

\ Ib = – 23.16 + j9.554<br />

= 25.05 157.6 o pu.<br />

I c = b I a1 + b 2 I a2 + I a0<br />

\ Ic = (– 0.5 + j0.866) (– j16.56) + (– 0.5 – j0.866) ( j10.192) + j6.37<br />

\ Ic = 23.16 + j9.554 = 25.05 22. 4°<br />

pu.<br />

Voltage of healthy phase,<br />

Va = 3Va1 = 3 × 0.2548 = 0.7644 pu.<br />

Example 10.4: A 30 MVA, 13.2 KV synchronous generator has a solidly grounded neutral. Its<br />

positive, negative and zero sequence impedances are 0.30, 0.40 and 0.05 pu respectively. Determine<br />

the following:<br />

(a) What value of reactance must be placed in the generator neutral so that the fault current<br />

for a line-to-ground fault of zero fault impedance shall not exceed the rated line current?<br />

(b) What value of resistance in the neutral will serve the same purpose?<br />

(c) What value of reactance must be placed in the neutral of the generator to restrict the fault<br />

current to ground to rated line current for a double line to ground fault?<br />

(d) What will be the magnitudes of the line currents when the ground current is restricted as<br />

above?